Load calculator
List what the generator has to run. We add up the power it needs while running (kW) and at the worst moment when things start (kVA), then show the generators that cover both where it's going.
1. What will it run?
Add each load the way you know it: from its data plate in watts or amps, as kW or kVA, or as a motor. Power factor is on the data plate or the manufacturer's sheet; heaters and other resistive loads are 1.0.
No loads yet. Add one below.
2. How do they start?
3. Where is it going?
Phase
Motor code letters
NEC 2008 Table 430.7(B), Locked-Rotor Indicating Code Letters (kVA per horsepower with locked rotor). We use the top of each letter's range.
| Code letter | kVA per HP, locked rotor |
|---|---|
| A | 0–3.14 |
| B | 3.15–3.54 |
| C | 3.55–3.99 |
| D | 4–4.49 |
| E | 4.5–4.99 |
| F | 5–5.59 |
| G | 5.6–6.29 |
| H | 6.3–7.09 |
| J | 7.1–7.99 |
| K | 8–8.99 |
| L | 9–9.99 |
| M | 10–11.19 |
| N | 11.2–12.49 |
| P | 12.5–13.99 |
| R | 14–15.99 |
| S | 16–17.99 |
| T | 18–19.99 |
| U | 20–22.39 |
| V | 22.4 and up |