Winco GRP460P4
The Winco GRP460P4 is a natural gas / LP generator set built in Le Center, Minnesota, rated at standby up to 440 kW (550 kVA) on natural gas at 277/480 V and 346/600 V, 400 kW on natural gas at 120/208 and 120/240 V, and 300 kW (375 kVA) on LP, all three-phase at 60 Hz. It is powered by a turbocharged 12-cylinder PSI 22L engine at 1800 RPM driving a brushless Stamford S4L1D-G41 alternator with MX341 PMG voltage regulation of +/- 1% and under 5% total harmonic distortion. It features a Basler DGC 2020HD controller, a 600 A adjustable shunt-trip main breaker, cam-lock receptacles, a containment skid and a 3,000 W block heater, and is available for stationary, mobile, standby, prime and well head applications. Sound level is 76 dB(A) at 7 meters at full load. Whether this unit is headed for a well head, a mobile setup or a standby pad, we'll get it running right and keep it that way with routine maintenance and load bank testing anywhere in New Mexico.
Voltage configurations
| Pick | Voltage | kW | kVA | Amps |
|---|---|---|---|---|
| 120/208 V 3-ph, LP | 300 | 375 | 1,041 | |
| 120/208 V 3-ph, NG | 400 | 500 | 1,388 | |
| 120/240 V 3-ph, LP | 300 | 375 | 900 | |
| 120/240 V 3-ph, NG | 400 | 500 | 1,201 | |
| 277/480 V 3-ph, LP | 300 | 375 | 451 | |
| 277/480 V 3-ph, NG | 440 | 550 | 661 | |
| 346/600 V 3-ph, LP | 300 | 375 | 361 | |
| 346/600 V 3-ph, NG | 440 | 550 | 529 |
Factory-set to the voltage you order.
- Rating
- 300 kW / 375 kVA
- Voltage
- 120/208 V 3-ph, LP, 1041 A
- Fuel
- Natural gas / LP
- Sound level
- 76 dB(A) at 23 ft, full load
- Warranty
- 1 year / 2,000 hours (see operator's manual)
- Lead time
- 14–20 weeks
Output at your site
About 293.1 kW · 366.4 kVA of 300 kW · 375 kVA rated · 2.3% lower
From the manufacturer's derate: 3% per 1,000 ft above 1,200 ft; 1% per 10 °F above 77 °F. An estimate; we confirm sizing with you before you buy.
How long it runs
- LP (propane)About 16 hours on a 500-gallon tank filled to 80%. Uses 25 gal/hr at 50% load.
- Natural gasRuns as long as the gas supply holds. Uses about 3,330 cu ft/hr at 50% load.
From the manufacturer's fuel-use figures; between the loads it lists we estimate in a straight line. LP tanks are counted at 80% full. Real runtime depends on the load, the weather and the engine's condition.